kVA and kW to Amps Chart (Single and Three Phase)

Full-load current for standard transformer and generator sizes at common voltages, calculated from I = kVA × 1000 ÷ (√3 × V) for three-phase and I = kVA × 1000 ÷ V for single-phase. Use the calculator for any other size, voltage or power factor.

kVA, kW and amps calculator

601.4 A

500 kVA = 400 kW at power factor 0.8 (three-phase, 480 V)

I = kVA × 1000 ÷ (√3 × V); kW = kVA × PF. Size cables and protection to your wiring code.

Standards and method

Every current is calculated from the formulas above. No values are typed in.

Maintained by Miguel Coelho. Updated . See our editorial policy.

Preview of the printable kVA and kW to Amps Chart (Single and Three Phase)

Printable kVA to amps chart

Full-load current for transformers and generators, single- and three-phase, 120 V to 600 V. Includes the exact definition, formulas, a worked example and sources. Conversion values are checked against the defining constants, and reference data is cited to its source, before the PDF is published.

Free to print, share and use in teaching materials with attribution (CC BY 4.0).

Also in the Electrician and Electronics Reference Pack, with related sheets in one PDF.

Download the kVA to amps chart PDFDownload this chart as CSVDownload this chart as JSONElectrical unit converters →

Full kVA to amps chart

Full-load current for transformers and generators, single- and three-phase, 120 V to 600 V. These are the same tables as the printable PDF. For: Electricians, electrical engineers, generator and transformer installers, facilities managers.

Key relationship
Apparent power S (kVA) = √3 × V(line) × I ÷ 1000 for three-phase; V × I ÷ 1000 for single-phase
Formula
I = kVA × 1000 ÷ (√3 × V); I = kW × 1000 ÷ (√3 × V × PF)
Reverse
kVA = √3 × V × I ÷ 1000; kW = kVA × PF
Worked example
500 kVA at 480 V three-phase: 500,000 ÷ (1.732 × 480) = 601.4 A
Rounding
Amps to 1 decimal place. Voltages are line-to-line for three-phase. Generators are usually rated at power factor 0.8.

Three-phase kVA to amps

Three-phase kVA to amps
kVA208 V220 V380 V400 V415 V440 V480 V600 V
38.37.94.64.34.23.93.62.9
616.715.79.18.78.37.97.25.8
925.023.613.713.012.511.810.88.7
1541.639.422.821.720.919.718.014.4
3083.378.745.643.341.739.436.128.9
45124.9118.168.465.062.659.054.143.3
50138.8131.276.072.269.665.660.148.1
75208.2196.8114.0108.3104.398.490.272.2
100277.6262.4151.9144.3139.1131.2120.396.2
112.5312.3295.2170.9162.4156.5147.6135.3108.3
125347.0328.0189.9180.4173.9164.0150.4120.3
150416.4393.6227.9216.5208.7196.8180.4144.3
200555.1524.9303.9288.7278.2262.4240.6192.5
225624.5590.5341.9324.8313.0295.2270.6216.5
250693.9656.1379.8360.8347.8328.0300.7240.6
300832.7787.3455.8433.0417.4393.6360.8288.7
4001,110.31,049.7607.7577.4556.5524.9481.1384.9
5001,387.91,312.2759.7721.7695.6656.1601.4481.1
6301,748.71,653.3957.2909.3876.5826.7757.8606.2
7502,081.81,968.21,139.51,082.51,043.4984.1902.1721.7
8002,220.62,099.51,215.51,154.71,113.01,049.7962.3769.8
1,0002,775.72,624.31,519.31,443.41,391.21,312.21,202.8962.3
1,2503,469.73,280.41,899.21,804.21,739.01,640.21,503.51,202.8
1,5004,163.63,936.52,279.02,165.12,086.81,968.21,804.21,443.4
2,0005,551.45,248.63,038.72,886.82,782.42,624.32,405.61,924.5
2,5006,939.36,560.83,798.43,608.43,478.03,280.43,007.02,405.6
3,0008,327.27,873.04,558.04,330.14,173.63,936.53,608.42,886.8

Single-phase kVA to amps

Single-phase kVA to amps
kVA120 V208 V220 V230 V240 V277 V
0.54.22.42.32.22.11.8
18.34.84.54.34.23.6
1.512.57.26.86.56.35.4
216.79.69.18.78.37.2
325.014.413.613.012.510.8
541.724.022.721.720.818.1
7.562.536.134.132.631.327.1
1083.348.145.543.541.736.1
15125.072.168.265.262.554.2
25208.3120.2113.6108.7104.290.3
37.5312.5180.3170.5163.0156.3135.4
50416.7240.4227.3217.4208.3180.5
75625.0360.6340.9326.1312.5270.8
100833.3480.8454.5434.8416.7361.0
1671,391.7802.9759.1726.1695.8602.9

Three-phase kW to amps at power factor 0.8 (generators)

Three-phase kW to amps at power factor 0.8 (generators)
kWkVA208 V400 V415 V480 V600 V
1012.534.718.017.415.012.0
202569.436.134.830.124.1
2531.386.745.143.537.630.1
3037.5104.154.152.245.136.1
4050138.872.269.660.148.1
5062.5173.590.287.075.260.1
6075208.2108.3104.390.272.2
7593.8260.2135.3130.4112.890.2
80100277.6144.3139.1120.396.2
100125347.0180.4173.9150.4120.3
125156.3433.7225.5217.4187.9150.4
150187.5520.4270.6260.9225.5180.4
200250693.9360.8347.8300.7240.6
250312.5867.4451.1434.8375.9300.7
3003751,040.9541.3521.7451.1360.8
4005001,387.9721.7695.6601.4481.1
5006251,734.8902.1869.5751.8601.4
6007502,081.81,082.51,043.4902.1721.7
750937.52,602.21,353.21,304.31,127.6902.1
8001,0002,775.71,443.41,391.21,202.8962.3
1,0001,2503,469.71,804.21,739.01,503.51,202.8
1,5001,8755,204.52,706.32,608.52,255.31,804.2
2,0002,5006,939.33,608.43,478.03,007.02,405.6

Three-phase amps to kVA

Three-phase amps to kVA
AmpskVA at 208 VkVA at 400 VkVA at 415 VkVA at 480 VkVA at 600 V
103.66.97.28.310.4
165.811.111.513.316.6
207.213.914.416.620.8
259.017.318.020.826.0
3211.522.223.026.633.3
4014.427.728.833.341.6
5018.034.635.941.652.0
6322.743.645.352.465.5
8028.855.457.566.583.1
10036.069.371.983.1103.9
12545.086.689.9103.9129.9
16057.6110.9115.0133.0166.3
20072.1138.6143.8166.3207.8
25090.1173.2179.7207.8259.8
400144.1277.1287.5332.6415.7
630227.0436.5452.8523.8654.7
800288.2554.3575.0665.1831.4
1,000360.3692.8718.8831.41,039.2
1,250450.3866.0898.51,039.21,299.0
1,600576.41,108.51,150.11,330.21,662.8
2,000720.51,385.61,437.61,662.82,078.5
2,500900.71,732.11,797.02,078.52,598.1
3,2001,152.92,217.02,300.22,660.43,325.5
4,0001,441.12,771.32,875.23,325.54,156.9

kW, kVA and kvar at different power factors

For 100 kW of load. Lower power factor means more current for the same real power.

kW, kVA and kvar at different power factors
Power factorkVA for 100 kWkvar for 100 kWAmps at 400 V 3-phaseAmps at 480 V 3-phase
0.60166.7133.3240.6200.5
0.70142.9102.0206.2171.8
0.75133.388.2192.5160.4
0.80125.075.0180.4150.4
0.85117.662.0169.8141.5
0.90111.148.4160.4133.6
0.95105.332.9151.9126.6
1.00100.00.0144.3120.3

Formulas

Motor full-load currents for conductor and protection sizing come from code tables (NEC 430.248–430.250) or the motor nameplate, not from these formulas.

Formulas
To findSingle-phaseThree-phaseDC
Amps from kVAI = kVA × 1000 ÷ VI = kVA × 1000 ÷ (√3 × V)—
Amps from kWI = kW × 1000 ÷ (V × PF)I = kW × 1000 ÷ (√3 × V × PF)I = kW × 1000 ÷ V
kVA from ampskVA = V × I ÷ 1000kVA = √3 × V × I ÷ 1000—
kW from ampskW = V × I × PF ÷ 1000kW = √3 × V × I × PF ÷ 1000kW = V × I ÷ 1000
kW from kVAkW = kVA × PFkW = kVA × PF—
Motor input kWkW = hp × 0.7457 ÷ efficiencykW = hp × 0.7457 ÷ efficiencykW = hp × 0.7457 ÷ efficiency

Sources for this chart

Every current is calculated from the formulas above. No values are typed in.

  • IEEE Std 1459 — Definitions of apparent (VA), active (W) and reactive (var) power
  • IEC 60038 — Standard voltages (230/400 V; 120/208 V, 277/480 V and 347/600 V systems in North America)

Related Converters & Charts

Share, cite or embed this kVA to amps chart

Free to use in teaching materials, intranets and resource pages under CC BY 4.0. Please keep the link to the source.

Embed this chart

Shows the printable sheet on your page, linked to the interactive version. Keep the caption: it is the attribution.

<figure style="margin:0;max-width:560px">
  <a href="https://allunitconversions.com/kva-to-amps-chart"><img src="https://allunitconversions.com/images/charts/kva-to-amps-chart.png" alt="kVA and kW to Amps Chart (Single and Three Phase) (printable)" width="560" height="792" loading="lazy" style="width:100%;height:auto;border:1px solid #e2e8f0"></a>
  <figcaption style="font-size:13px;line-height:1.4"><a href="https://allunitconversions.com/kva-to-amps-chart">kVA and kW to Amps Chart (Single and Three Phase)</a> by Miguel Coelho, All Unit Conversions (free to share, CC BY 4.0)</figcaption>
</figure>

Link to it

For resource lists, course pages and wikis.

<a href="https://allunitconversions.com/kva-to-amps-chart">kVA and kW to Amps Chart (Single and Three Phase)</a> (All Unit Conversions)

Cite it

Suggested citation for reports, coursework and slides.

Coelho, M. (2026). kVA and kW to Amps Chart (Single and Three Phase) (Edition 2.0). All Unit Conversions. https://allunitconversions.com/kva-to-amps-chart

kVA and kW to Amps Chart (Single and Three Phase) FAQs

Common questions about the kVA to amps chart.

How many amps is 500 kVA at 480 V three phase?

I = 500,000 ÷ (√3 × 480) = 601.4 A. At 400 V it is 721.7 A and at 208 V it is 1,387.9 A.

How do you convert kW to amps?

Divide by the voltage and the power factor: I = kW × 1000 ÷ (√3 × V × PF) for three-phase, or kW × 1000 ÷ (V × PF) for single-phase. A 100 kW generator at power factor 0.8 and 480 V delivers 150.4 A.

What is the difference between kVA and kW?

kVA is apparent power (volts × amps); kW is the real power that does work. kW = kVA × power factor, so a 100 kVA generator rated at power factor 0.8 supplies 80 kW.

Can I download this chart as a PDF, CSV, or JSON?

Yes. Use the Download A4 PDF or US Letter PDF buttons for a printable version, or download the same tables as CSV or JSON from the links on this page.