AWG Wire Size Chart (Gauge to mm, mm² and kcmil)

Every American Wire Gauge size from 4/0 to 40, calculated from the ASTM B258 definition, with copper resistance at 20 °C and the nearest IEC 60228 metric cable size. Current ratings depend on the installation, so use your wiring code for those.

Standards and method

Diameters and areas are calculated from the AWG definition; resistance uses the IEC 60028 copper resistivity; the nearest metric size is the IEC 60228 cross-section closest in area.

Maintained by Miguel Coelho. Updated . See our editorial policy.

Preview of the printable AWG Wire Size Chart (Gauge to mm, mm² and kcmil)

Printable AWG wire size chart

American Wire Gauge 4/0 to 40: diameter, area in mm² and kcmil, copper resistance and nearest metric size. Includes the exact definition, formulas, a worked example and sources. Conversion values are checked against the defining constants, and reference data is cited to its source, before the PDF is published.

Free to print, share and use in teaching materials with attribution (CC BY 4.0).

Also in the Electrician and Electronics Reference Pack, with related sheets in one PDF.

Download the AWG wire size chart PDFDownload this chart as CSVDownload this chart as JSONElectrical unit converters →

Full AWG wire size chart

American Wire Gauge 4/0 to 40: diameter, area in mm² and kcmil, copper resistance and nearest metric size. These are the same tables as the printable PDF. For: Electricians, electronics engineers, installers, makers and students.

Key relationship
AWG 36 = 0.005 in and AWG 4/0 = 0.46 in; 39 steps between them (ASTM B258)
Formula
d = 0.005 in × 92^((36 − n) ÷ 39)
Reverse
n = 36 − 39 × log₉₂(d ÷ 0.005 in)
Worked example
AWG 12: 0.0808 in = 2.053 mm, 3.31 mm²
Rounding
Solid round copper at 20 °C, 1/58 Ω·mm²/m (IEC 60028). Every 6 gauges halves the diameter; every 3 gauges halves the area.

AWG sizes, dimensions and copper resistance

Nearest metric size is the closest IEC 60228 cross-section by area. It is not a substitute for sizing a cable to your wiring code.

AWG sizes, dimensions and copper resistance
AWGDiameter (in)Diameter (mm)Area (mm²)Area (kcmil)Ω per kmΩ per 1000 ftNearest mm²
4/0 (0000)0.460011.684107.2211.60.16080.04901120
3/0 (000)0.409610.40585.03167.80.20280.061895
2/0 (00)0.36489.26667.43133.10.25570.0779370
1/0 (0)0.32498.25153.48105.50.32240.0982750
10.28937.34842.4183.690.40660.123950
20.25766.54433.6366.370.51270.156335
30.22945.82726.6752.630.64650.19725
40.20435.18921.1541.740.81520.248525
50.18194.62116.7733.11.0280.313316
60.16204.11513.326.251.2960.395116
70.14433.66510.5520.821.6340.498210
80.12853.2648.36616.512.0610.628210
90.11442.9066.63413.092.5990.79216
100.10192.5885.26110.383.2770.99896
110.09072.3054.1728.2344.1321.264
120.08082.0533.3096.535.2111.5884
130.07201.8282.6245.1786.5712.0032.5
140.06411.6282.0814.1078.2862.5252.5
150.05711.4501.653.25710.453.1841.5
160.05081.2911.3092.58313.174.0161.5
170.04531.1501.0382.04816.615.0641
180.04031.0240.8231.62420.956.3850.75
190.03590.9120.65271.28826.428.0510.75
200.03200.8120.51761.02233.3110.150.5
210.02850.7230.41050.81014212.80.5
220.02530.6440.32550.642452.9616.14—
230.02260.5730.25820.509566.7920.36—
240.02010.5110.20470.40484.2225.67—
250.01790.4550.16240.3204106.232.37—
260.01590.4050.12880.2541133.940.81—
270.01420.3610.10210.2015168.951.47—
280.01260.3210.080980.1598212.964.9—
290.01130.2860.064220.1267268.581.84—
300.01000.2550.050930.1005338.6103.2—
310.00890.2270.040390.0797426.9130.1—
320.00800.2020.032030.06321538.3164.1—
330.00710.1800.02540.05013678.8206.9—
340.00630.1600.020140.03975856260.9—
350.00560.1430.015970.031521,079329—
360.00500.1270.012670.0251,361414.8—
370.00450.1130.010050.019831,716523.1—
380.00400.1010.0079670.015722,164659.6—
390.00350.0900.0063180.012472,729831.8—
400.00310.0800.005010.0098883,4411,049—

Metric cable sizes (IEC 60228) to AWG

Metric cable sizes (IEC 60228) to AWG
Area (mm²)Solid diameter (mm)Area (kcmil)Nearest AWGΩ per km (copper)
0.50.800.98682034.48
0.750.981.481822.99
11.131.9741717.24
1.51.382.961511.49
2.51.784.934136.897
42.267.894114.31
62.7611.8492.874
103.5719.7471.724
164.5131.5851.078
255.6449.3430.6897
356.6869.0720.4926
507.9898.681/0 (0)0.3448
709.44138.12/0 (00)0.2463
9511.00187.53/0 (000)0.1815
12012.36236.84/0 (0000)0.1437
15013.822964/0 (0000)0.1149
18515.35365.14/0 (0000)0.0932
24017.48473.64/0 (0000)0.07184
30019.54592.14/0 (0000)0.05747
40022.57789.44/0 (0000)0.0431
50025.23986.84/0 (0000)0.03448
63028.321,2434/0 (0000)0.02737

Using this chart

Using this chart
PointWhat to know
Stranded wireA stranded conductor of the same gauge has about the same copper area but a slightly larger overall diameter.
Resistance and temperatureCopper resistance rises about 0.393% per °C above 20 °C; at 75 °C it is about 22% higher than shown.
Current ratingAmpacity depends on insulation, installation method, bundling and ambient temperature. Use NEC Table 310.16, BS 7671 or IEC 60364-5-52.
kcmil and MCM1 kcmil = 1,000 circular mils = 0.5067 mm². Sizes above 4/0 are named in kcmil (250, 300, 350 …).
Voltage dropTwo-wire drop = 2 × length × current × Ω per unit length. Many codes recommend no more than 3% to 5%.

Sources for this chart

Diameters and areas are calculated from the AWG definition; resistance uses the IEC 60028 copper resistivity; the nearest metric size is the IEC 60228 cross-section closest in area.

  • ASTM B258 — Standard nominal diameters and cross-sectional areas of AWG sizes of solid round wires
  • IEC 60028 — International standard of resistance for copper: 1/58 Ω·mm²/m at 20 °C (100% IACS)
  • IEC 60228 — Conductors of insulated cables: nominal cross-sectional areas

Related Converters & Charts

Share, cite or embed this AWG wire size chart

Free to use in teaching materials, intranets and resource pages under CC BY 4.0. Please keep the link to the source.

Embed this chart

Shows the printable sheet on your page, linked to the interactive version. Keep the caption: it is the attribution.

<figure style="margin:0;max-width:560px">
  <a href="https://allunitconversions.com/awg-wire-size-chart"><img src="https://allunitconversions.com/images/charts/awg-wire-size-chart.png" alt="AWG Wire Size Chart (Gauge to mm, mm² and kcmil) (printable)" width="560" height="792" loading="lazy" style="width:100%;height:auto;border:1px solid #e2e8f0"></a>
  <figcaption style="font-size:13px;line-height:1.4"><a href="https://allunitconversions.com/awg-wire-size-chart">AWG Wire Size Chart (Gauge to mm, mm² and kcmil)</a> by Miguel Coelho, All Unit Conversions (free to share, CC BY 4.0)</figcaption>
</figure>

Link to it

For resource lists, course pages and wikis.

<a href="https://allunitconversions.com/awg-wire-size-chart">AWG Wire Size Chart (Gauge to mm, mm² and kcmil)</a> (All Unit Conversions)

Cite it

Suggested citation for reports, coursework and slides.

Coelho, M. (2026). AWG Wire Size Chart (Gauge to mm, mm² and kcmil) (Edition 2.0). All Unit Conversions. https://allunitconversions.com/awg-wire-size-chart

AWG Wire Size Chart (Gauge to mm, mm² and kcmil) FAQs

Common questions about the AWG wire size chart.

How thick is 12 AWG wire?

12 AWG solid wire is 0.0808 in (2.053 mm) in diameter with a cross-section of 3.31 mm² (6.53 kcmil). Its copper resistance is about 5.21 Ω per km at 20 °C.

What metric size is closest to 14 AWG?

14 AWG is 2.08 mm², so the nearest IEC 60228 size is 2.5 mm². 12 AWG (3.31 mm²) is nearest to 4 mm², and 10 AWG (5.26 mm²) to 6 mm². Size cables for current to your local wiring code.

Why does a larger AWG number mean a thinner wire?

AWG numbers count drawing steps: each step makes the wire thinner. Every 6 gauges halve the diameter and every 3 gauges halve the cross-sectional area.

Can I download this chart as a PDF, CSV, or JSON?

Yes. Use the Download A4 PDF or US Letter PDF buttons for a printable version, or download the same tables as CSV or JSON from the links on this page.